Publication 1747-UM002A-US-P - June 2000
6-24 Library of Routines
OC_GetMeasuredScan
Time
OC_GetMeasuredScanTime returns the maximum and last observed I/
O scan times.
Syntax:
int OC_GetMeasuredScanTime(HANDLE Handle, WORD
*maxtime, WORD *lasttime);
Parameters:
Description:
The scanner calculates these values at the end of each I/O scan. The
values are represented in units of 250 microseconds.
The scan times are reset to zero when changing to Scan mode, and
are not valid until the end of the second I/O scan. Only the timed I/O
scans are measured; the demand input or output scans are not.
Return Value:
Considerations:
Supported in the DOS API library and the Windows NT API library
Example:
HANDLE Handle;
WORD max_time, last_time;
int retcode;
retcode = OC_GetMeasuredScanTime( Handle, &max_time,
&last_time );
Parameter: Description:
handle Must be a valid handle returned from OC_OpenScanner
maxtime Returns the maximum scan time
lasttime Returns the last scan time
Name: Value: Description:
SUCCESS 0 measured scan time was read successfully
ERR_OCACCESS 2
handle does not have access to scanner
ERR_OCINIT 5 scanner has not been initialized, see OC_InitScanner