18 Compact I/O 1769-ADN DeviceNet Adapter
Rockwell Automation Publication 1769-IN001C-EN-P - February 2013
Configuring the 1769-ADN Series B Adapter
The 1769-ADN must be configured with RSNetWorx for DeviceNet software. This
configuration tool allows you to identify all of the devices (I/O modules, power supplies,
expansion cables, end caps) and their locations in your 1769 system. The 1769-ADN must have
the I/O configuration loaded into its’ memory to perform the network communication
function.
The 1769-ADN does not accept I/O connections if the programmed system configuration does
not match the actual system configuration. The 1769-ADN retains the programmed system
configuration in non-volatile memory so it can compare it with the actual system configuration
on power-up. For more information, refer to the
Compact I/O 1769-ADN DeviceNet Adapter
User
Manual, publication 1769-UM001
.
I/O Memory Mapping
Output Data
This is the I/O data the DeviceNet master sends to the 1769-ADN. All outputs are in words. For
more information, refer to the
Compact I/O 1769-ADN DeviceNet Adapter
User Manual
publication 1769-UM001
.
Word
Bit Position
1514131211109876543210
0 Output data for slot 1*
1“
““
n Output data for slot 30*
* = The amount of output data for each module is based on the configuration of each I/O module done as part of the 1769-ADN
configuration. Note that if an I/O module is configured to have 0 words of output data, then there are no output data words for that
module in the 1769-ADN’s output image.