Input Data
This is the I/O data the 1769-ADN sends to the DeviceNet master. All inputs are in words. For
more information, refer to the
Compact I/O 1769-ADN DeviceNet Adapter
User Manual,
publication 1769-UM001
.
Word
Bit Position
1514131211109876543210
0 V16 V15 V14 V13 V12 V11 V10 V9 V8 V7 V6 V5 V4 V3 V2 V1
1 X NS V30 V29 V28 V27 V26 V25 V24 V23 V22 V21 V20 V19 V18 V17
2 Input data for slot 1*
3“
““
n Input data for slot 30*
* = The amount of input data for each module is based on the configuration of each I/O module done as part of the 1769-ADN configuration. Note that if an I/O
module is configured to have 0 words of input data, then there are no input data words for that module in the 1769-ADN’s input image.
V1 = Data invalid from slot 1 (1 = invalid data)
V2 = Data invalid from slot 2
V3 = Data invalid from slot 3
...
V30 =Data invalid from slot 30
where 1 = data invalid or a module error is detected; 0 = data valid, no module error
NS = Node address switch changed
where 1 = node address switch changed since power-up
X = Reserved