2–6 Installing Your Module
Publication 1771-UM001A-US-P - February 2000
Figure 2.5
Module Switch Assembly Settings for PLCĆ3 Family
Processors
1 2 3 4 56 78
First I/O group number
(Table 2.B)
I/O rack number
(Table 2.B)
Address Switch Assembly
(S1)
Switch Assembly (S2)
Pressed in at top
(ON)
Pressed in at bottom
(OFF)
1234
56
Switch Position
12
57.6K Baud Ć 10,000ft
115.2K Baud Ć 5,000ft
Not Used
Maximum I/O
chassis distance
Link Response Ć ON for series B emulation
Scan Ć ON for all but last 4 slots
OFF for all slots
OFF for unrestricted
Always OFF
10799ĆI
ATTENTION: Link response switch must
be ON when using the following scanner
modules:
1775ĆS4A
1775ĆS4B
1775ĆS5
1775ĆSR5
1775ĆSR
ON OFF
OFF OFF
ON ON
ON 230.4K Baud Ć 2,500ft
1
OFF
1 230.4K Baud with 1775ĆS5 revision A/G, and
1775ĆSR5 revision A/G scanners only.
Off
(ON)
(OFF)
(ON)
(OFF)
OPEN
OPEN
Table 2.B
I/O Rack Switch Selections for the Address Switch
Assembly (PLCĆ3 Family Processors)
Rack
#
Switch Setting
1 2 345 6
Rack
#
Switch Setting
1 2 345 6
Rack
#
Switch Setting
1 2 345 6
Rack
#
Switch Setting
1 2 345 6
00 On On On On On On 20 On Off On On On On 40 Off On On On On On 60 Off Off On On On On
01 On On On On On Off 21 On Off On On On Off 41 Off On On On On Off 61 Off Off On On On Off
02 On On On On Off On 22 On Off On On Off On 42 Off On On On Off On 62 Off Off On On Off On
03 On On On On Off Off 23 On Off On On Off Off 43 Off On On On Off Off 63 Off Off On On Off Off
04 On On On Off On On 24 On Off On Off On On 44 Of On On Off On On 64 Off Off On Off On On
05 On On On Off On Off 25 On Off On Off On Off 45 Off On On Off On Off 65 Off Off On Off On Off
06 On On On Off Off On 26 On Off On Off Off On 46 Off On On Off Off On 66 Off Off On Off Off On
07 On On On Off Off Off 27 On Off On Off Off Off 47 Off On On Off Off Off 67 Off Off On Off Off Off
10 On On Off On On On 30 On Off Off On On On 50 Off On Off On On On 70 Off Off Off On On On
11 On On Off On On Off 31 On Off Off On On Off 51 Off On Off On On Off 71 Off Off Off On On Off
12 On On Off On Off On 32 On Off Off On Off On 52 Off On Off On Off On 72 Off Off Off On Off On
13 On On Off On Off Off 33 On Off Off On Off Off 53 Off On Off On Off Off 73 Off Off Off On Off Off
14 On On Off Off On On 34 On Off Off Off On On 54 Off On Off Off On On 74 Off Off Off Off On On
15 On On Off Off On Off 35 On Off Off Off On Off 55 Off On Off Off On Off 75 Off Off Off Off On Off
16 On On Off Off Off On 36 On Off Off Off Off On 56 Off On Off Off Off On 76 Off Off Off Off Off On
17 On On Off Off Off Off 37 On Off Off Off Off Off 57 Off On Off Off Off Off 77 Not valid
1st I/O Group
Number
Switch Selections
78
Note: Rack address 77 is an illegal configuration.
PLCĆ3 processors can scan racks 0Ć76.
0 On On
2 On Off
4 Off On
6 Off Off