3–10 Addressing Modes for Your Remote I/O
0(& /&+* "-0-3
Follow these guidelines when configuring your remote system with
complementary I/O chassis:
• Assign the complementary I/O rack number to a chassis of equal
or smaller size than the primary chassis.
• If the complementary chassis is smaller than the primary one, set
the last chassis switch on the complementary chassis to the ON
position, unless the adapter is in the faulted I/O search mode.
• For PLC-2 family processors:
• Connect the complementary chassis to the same scanner
channel as the primary chassis.
• Connect the complementary chassis to the remote trunkline as
though they were additional primary chassis.
• For PLC-3 processors, connect the complementary chassis to a
different scanner channel as the primary chassis.
• Assign the same beginning I/O group number to both I/O racks.
• You cannot configure complementary I/O in a chassis that uses a
combination of 2-slot addressing and 16-point I/O.
• You cannot use 32-point I/O modules in a complementary I/O
configuration when you select 2-slot or 1-slot addressing.
• You can place an output module opposite another output
module; they reflect the same bits in the output image table.
• Do not place an input module opposite an input module.
You can use the following modules in either primary or
complementary I/O chassis opposite any type of module:
Catalog Number Description
4 4 4 *(+$ *,0/ 2,*!"- ..")(3
4 *(+$ 0/,0/ 2,*!"- ..")(3
4 %"-)+ +0,(" *,0/ 2,*!"- +!0(" ..")(3
4 "-1+ * +!"- ""! ' 2,*!"- ..")(3
4 +))0*& /&+* !,/"- +!0("
4 +))0*& /&+* +*/-+(("- +!0("
4 4 )&(344 */"-# " +!0("
4 0(." 0/,0/ 2,*!"- ..")(3
4 &"- ,/& . +*1"-/"- +!0("
Comentarios a estos manuales