Rockwell-automation 1771-DB BASIC MODULE Manual de usuario Pagina 239

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 394
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 238
Chapter
Call Routines 0–68
12
12 -49
Example
>10
REM ENABLE REMOTE DH-485 READ COMMAND INTERRUPT
>
15 PUSH 64: CALL 4: REM SET BLOCK TRANSFER WRITE LENGTH
>
16 PUSH 64: CALL 5: REM SET BLOCK TRANSFER READ LENGTH
>
20 PUSH 2 : REM SLC TYPED READ COMMAND
>
30 PUSH 2 : REM NODE ADDRESS OF REMOTE SLC
>
40 PUSH 7 : REM FILE NUMBER OF REMOTE SLC
>
50 PUSH ASC(N) : REM FILE TYPE OF REMOTE SLC
>
60 PUSH 100 :REM REMOTE ELEMENT OFFSET INTO REMOTE SLC FILE
>
70 PUSH 20 : REM NUMBER OF ELEMENTS TO BE TRANSFERRED
>
80 PUSH 5 : REM MESSAGE TIMEOUT (X100MS)
>
90 PUSH 0 : REM DESTINATION FILE TO PUT DATA (BTR BUFFER)
>
100 PUSH 1 : REM ALWAYS 1
>
110 PUSH 0 :REM STRING NUMBER–NOT AVAILABLE FOR THIS EXAMPLE
>
120 CALL 49
>
130 POP S
>
140 IF (S<>0) THEN PRINT “UNSUCCESSFUL CALL 49 SETUP”
Sample Ladder Logic
(L)
O:001
14
BTR
BLOCK TRANSFER READ
Rack
Group
Module
00
1
0
N7:0
N10:10
64
Control Block
Data file
Length
Rung 2:0
14
I:001
Rung 2:2
[END OF FILE]
(EN)
(DN)
(ER)
N
Continuous
N10:0
0
Rung enable bit
(N10:0 used as example)
(U)
N10:0
Rung 2:1
(U)
O:001
14
0
O:001
14
Vista de pagina 238
1 2 ... 234 235 236 237 238 239 240 241 242 243 244 ... 393 394

Comentarios a estos manuales

Sin comentarios