Rockwell-automation 1771-DB BASIC MODULE Manual de usuario Pagina 32

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 394
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 31
Chapter
Installing the BASIC Module
1
1 -8
Set PRT2 Communication Rate Select Jumper (JW6)
Use JW6 to set the communication rate for PRT2 at power-up.
Set the communication rate according to your application.
Important: You can also select the communication rate for PRT2 within
your program. The settings you select with PROG1 (page 10 -12) and
PROG2 (page 10 -13) override the jumper setting until the module is
powered down. The settings you select with MODE (page 11 -20)
override both the jumper and the PROG1 and PROG2 settings until the
module is powered down. If you use PROG1, PROG2, or MODE with the
“E” option storage to save the port settings in the user EEPROM, the unit
then powers up with the stored configuration.
To set the communication rate for:
Se
t j
u
mp
er
:
your selection:
300 bit/s
600 bit/s
1200 bit/s
factory
setting
2400 bit/s
4800 bit/s
9600 bit/s
19.2k bit/s
Refer to Chapter 2 for more information regarding communication rates.
Chapter
Vista de pagina 31
1 2 ... 27 28 29 30 31 32 33 34 35 36 37 ... 393 394

Comentarios a estos manuales

Sin comentarios