Chapter
Call Routines 69–127
13
13 -12
Use CALL 84 to transfer up to 40 words starting at the designated offset of
the DH-485 Common Interface File to the BASIC module input buffer
starting at the same designated offset from word 0.
This call does not interrupt nor is it interrupted by a DH-485 read or write
from or to the DH-485 common interface file.
Input and Output Arguments
This routine has two input arguments and one output argument. The first
input argument is the starting offset in the DH-485 Common Interface File
and the BASIC module input buffer (100 to 139). The second input
argument is the length in words to be transferred (1 to 40). The output
argument is the status of the call:
0 = successful transfer
1 = illegal starting offset; transfer does not take place
2 = illegal length; transfer does not take place
Syntax
PUSH
starting word offset in DH-485 interface file
PUSH number of words to be transferred
CALL
84
POP transfer status
Example
>1
REM EXAMPLE PROGRAM
>
40 PUSH 0 : REM OFFSET ADDRESS = 0
>
50 PUSH 32 : REM WORD OFFSET = 32
>
60 CALL 84 : REM TRANSFER THE DATA TO THE BASIC INPUT BUFFER
>
70 POP R : REM GET THE OUTPUT ARGUMENT
>
80 IF (R<>0) THEN PRINT “TRANSFER ERROR CODE = ”,R
>90 REM PRINT ERROR
CALL
84: T
ransfer DH-485
Common Interface File to
BASIC Input Buffer