
Chapter
5
5-1
Module Status and Input Data
In this chapter you will read about:
reading data from your module
block transfer read block format
Block transfer read programming moves status and data from the input
module to the processor’s data table in one I/O scan (Figure 5.1). The
processor’s user program initiates the request to transfer data from the
input module to the processor.
Figure 5.1
Word
Assignments for Analog Input Module (1771IFE)
Block T
ransfer Read
Decimal Bits 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Description
Octal Bits 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00
Description
Word 1 Not Used Diagnostic Bits Diagnostics
2 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 Data underrange for channels 1-16
1
3 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 Data overrange for channels 1-16
1
4 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 Data polarity for channels 1-16
5 Channel 1 Input Channel 1 Input
6 Channel 2 Input Channel 2 Input
7 Channel 3 Input Channel 3 Input
8 Channel 4 Input Channel 4 Input
⇓⇓⇓⇓
20 Channel 16 Input Channel 16 Input
1
These
bits are set (1) at approximately the input range limits selected (
Table 5.B).
Chapter
Objectives
Reading Data From Your
Module
Comentarios a estos manuales