Chapter
6
6-1
Calibrating Your Module
In this chapter we tell you what tools you need and how to calibrate your
module.
In order to calibrate your input module you will need the following tools
and equipment:
Equipment Description
Digital voltmeter
51/2 digit, 0.01% accuracy minimum: Keithley191 or Fluke
8300A or equivalent
Alignment tool
P/n 35F616, for pot adjustment: Newark Electronics,
500 N.Pulaski Rd., Chicago, IL
Potentiometer sealant
Torque Seal: Organic Products,
P.O. Box 928, Irving, TX
Industrial terminal
Cat. no. 1770T3 and program panel interconnect cable
(cat. no. 1772TC) for PLC2 family processors:
AllenBradley,Highland Hts., OH
Backplane extender card Cat. no. 1771EZ
The analog input module is shipped from the factory already calibrated.
If necessary to recalibrate the module, you must calibrate the module in an
I/O chassis. The module must communicate with the processor and
industrial terminal. Calibration consists of adjusting the 10V reference and
nulling the input offset.
Important: The module must be powered up for at least 30 minutes before
attempting to calibrate.
ATTENTION: Do not attempt to calibrate your module until
you have read and thoroughly understand this procedure. Also,
do not attempt to calibrate this module in an operating system.
Damage to the equipment or personal injury may result.
Chapter
Objectives
Tools and Equipment
Calibration Procedure