Publication 1771-6.5.119
Install the Module 2-9
Single-point Grounding
19923-M
Extend shield to termination point.
Expose just enough cable to adequately
terminate inner conductors.
Use heat shrink tubing or
other suitable insulation
where wire exits cabe
jacket.
Shield and Drain
twisted together
#10 Thread-forming screw
External-tooth
washer