Rockwell-automation 1771-IR , D17716.5.76 RTD INPUT MODULE Manual de usuario Pagina 31

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 68
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 30
Chapter
6
61
Module Status and Input Data
In this chapter you will read about:
reading data from your module
input module read block format
Block transfer read programming moves status and data from the input module
to the processors data table in one I/O scan (Table 6.A). The processor user
program initiates the request to transfer data from the input module to the
processor.
During normal operation, the read block transfer for this module moves up to 8
words from the RTD module in one program scan. The words contain module
status and input data from each channel. When a block transfer length of 0 is
programmed, the 1771–IR/B will respond with the Series A default of 8
words.
The user program initiates the request to transfer data from the RTD module to
the processor.
Table 6.A
BTR
W
ord Assignments for RTD Input Module (1771-IR/B)
Decimal Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Octal Bit 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00
1 0 RTS
Timeout
Channel Overrange
EEPROM
calibration
values not
readable
Power-
up
Channel Underrange
2 Not used Channel Polarity Not used Channel Overflow
3 Channel 1 Data
4 Channel 2 Data
5 Channel 3 Data
6 Channel 4 Data
7 Channel 5 Data
8 Channel 6 Data
9 Auto-calibration Status Word
Chapter Objectives
Reading Data from the RTD
Module
Vista de pagina 30