Programming Examples
Appendix B
B5
Figure B.3
Sample
PLC-5 Data File (Hexidecimal Data)
Address
N7:60
N7:70
3
0150
0000
5
0150
6
0150
7
0150
8
0000
9
0000
4
0150
2
0150
0000
1
0976
0000
0
5141
0000
The above data file would configure the module as follow:
copper RTDs on all inputs
temperature scale of Fahrenheit
channel 1 displayed in ohms
output data in BCD format
real time sampling set to a 1 second scan rate
copper RTD at 25
o
C is 9.76 ohms
all bias values set to subtract 0150
all calibration values set to 0
3. Enter the data corresponding to your bit selections.
4. [ESC] returns you to the main menu.