Appendix D
Publication 1771ĆUM127B-EN-P - December 2002
Block Transfer Write and Block
Transfer Read Configurations
for 2 Output/2 Input 1771ĆN
Series Modules
This appendix contains block transfer write and block transfer read
configurations and bit/word descriptions for 1771-N series modules
with two outputs and two inputs.
Block Transfer Write Configuration Block for the 2 Output/2 Input
Modules
Word/Dec. Bit
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Word/Octal Bit
17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00
BTW word type Constant Number of outputs Constant
010 0 0 1 0 0 0 0 0 1 0 0 0 0 0
1 Channel 1 Output Data
2 Channel 2 Output Data
3
CJ alarm
enable
Unused = 0
BCD
select
Temp
scale
Verify
4 RTS Sample Time: 1 millisecond units
Channel 1 Programming
5 Low Scale Value
6 High Scale Value
7 Low Clamp Value
8 High Clamp Value
9
Alarm
enable
Reset State 0 Maximum Ramp Rate, % of Full Scale per second
10 Reset Value
Channel 2 Programming
11 Low Scale Value
12 High Scale Value
13 Low Clamp Value
14 High Clamp Value
15
Alarm
enable
Reset State 0 Maximum Ramp Rate, % of Full Scale per second
16 Reset Value
Channel 3 Programming
17 Low Scale Value
What This Appendix