Rockwell-automation 1771-N SERIES High Resolution Analog Module User M Manual de usuario Pagina 155

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 188
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 154
Block Transfer Write and Block Transfer Read Configurations for 6 Output/2 Input 1771-N Series Modules I–3
Publication 1771ĆUM127B-EN-P - December 2002
00010203040506070809101112131415
Word/Dec. Bit
00010203040506071011121314151617
Word/Octal Bit
44 Reset Value
Channel 7 Programming
45 Low Scale Value
46 High Scale Value
47 Low Alarm Value
48 High Alarm Value
49
Alarm
enable
Rate Alarm: Scaled Units per second
50 Filter Time Constant: 0.1 second units Alarm Deadband
51 Thermocouple Type 0 RTD Type 10 Ohm Offset: 0.01 Ohm units
Channel 8 Programming
52 Low Scale Value
53 High Scale Value
54 Low Alarm Value
55 High Alarm Value
56
Alarm
enable
Rate Alarm: Scaled Units per second
57 Filter Time Constant: 0.1 second units Alarm Deadband
58 Thermocouple Type 0 RTD Type 10 Ohm Offset: 0.01 Ohm units
Block Transfer Write Bit/Word Descriptions for 6 Output/2 Input
Modules
Word
Decimal Bit
(Octal Bit)
Definition
00-03 Constant = 0
Bits 04-07 Number of outputs = 0110 binary
Word 0
Bits 08-13
(10-15)
Constant = 00 1000 binary
Bits 14-15
(16-17)
Block transfer write type = 10 binary
Word 1
Bits 00-15
(00-17)
First Output channel data
Word 2
Bits 00-15
(00-17)
Second Output channel data
Word 3
Bits 00-15
(00-17)
Third Output channel data
Word 4
Bits 00-15
(00-17)
Fourth Output channel data
Vista de pagina 154