ControlNet PLC-5 Hot Backup SystemCat. No. 1785-CHBMUser Manual
Publication 1785-UM024B-EN-P - January 2003Summary of Changes 2Notes
Publication 1785-UM024B-EN-P - January 2003C-2 Data Table CrossloadingAn On-Demand data table crossload transfers data table data from the prim
Publication 1785-UM024B-EN-P - January 2003Data Table Crossloading C-3On-Demand Data Table CrossloadsIt may be necessary for you to crossload d
Publication 1785-UM024B-EN-P - January 2003C-4 Data Table Crossloading• PD FilesThe entire PD file structure is crossloaded during the On-Deman
Publication 1785-UM024B-EN-P - January 2003Data Table Crossloading C-5– ControlNet I/O Status File– ControlNet Diagnostic FileOptimizing On-Dem
Publication 1785-UM024B-EN-P - January 2003C-6 Data Table CrossloadingThe On-Demand data table crossload operations that get performed depend o
Publication 1785-UM024B-EN-P - January 2003Data Table Crossloading C-7Qualification Data Table CrossloadThe Qualification data table crossload
Publication 1785-UM024B-EN-P - January 2003C-8 Data Table CrossloadingThe Qualification State data table crossload is almost identical to the O
Publication 1785-UM024B-EN-P - January 2003Data Table Crossloading C-9Effect of Data Table Crossloading on the ControlNet ChannelData table cro
Publication 1785-UM024B-EN-P - January 2003C-10 Data Table CrossloadingThese error codes are identical to the Message Instruction Error Codes.
1 Publication 1785-UM024B-EN-P - January 2003Appendix DProgram SynchronizationChapter ObjectivesThis appendix provides you with reference information
iii Publication 1785-UM024B-EN-P - January 2003Table of ContentsPrefaceManual Objectives. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Publication 1785-UM024B-EN-P - January 2003D-2 Program SynchronizationDetermining Which Mode to UseDetermining whether to select Asynchronous m
Publication 1785-UM024B-EN-P - January 2003Program Synchronization D-3Because every program scan is pushed out to the Maximum Program Scan Time
Publication 1785-UM024B-EN-P - January 2003D-4 Program SynchronizationShould frequent program scan overruns occur, it may be necessary for you
1 Publication 1785-UM024B-EN-P - January 2003Appendix EApplication GuidelinesChapter ObjectivesThis Appendix will provide you with application example
Publication 1785-UM024B-EN-P - January 2003E-2 Application GuidelinesSwitchover ConsiderationsThe following sections provide information on fac
Publication 1785-UM024B-EN-P - January 2003Application Guidelines E-3What Information Should Be Transferred?The secondary PLC-5 transfers selec
Publication 1785-UM024B-EN-P - January 2003E-4 Application GuidelinesIf the secondary begins execution with the control register at a different
Publication 1785-UM024B-EN-P - January 2003Application Guidelines E-5Performance ConsiderationsOne approach to redundant system design is to tr
Publication 1785-UM024B-EN-P - January 2003E-6 Application GuidelinesIt is also important that the secondary PLC-5 remains at the same state wi
Publication 1785-UM024B-EN-P - January 2003Application Guidelines E-7Data table values can become outdated because the data table crossload is
Publication 1785-UM024B-EN-P - January 2003Table of Contents ivAdvanced Configuration Options . . . . . . . . . . . . . . . . . . . . 3-18Confi
Publication 1785-UM024B-EN-P - January 2003E-8 Application GuidelinesHow to Keep the Hot Backup Programmable Controllers in the Same Process St
Publication 1785-UM024B-EN-P - January 2003Application Guidelines E-9How to Complete Qualification in the Same Process StateDuring qualificatio
Publication 1785-UM024B-EN-P - January 2003E-10 Application GuidelinesNotes
1 Publication 1785-UM024B-EN-P - January 2003Appendix FComparison to the 1785-BCM SystemChapter ObjectivesThis appendix provides you with a comparison
Publication 1785-UM024B-EN-P - January 2003F-2 Comparison to the 1785-BCM SystemIn terms of how data is provided to the two PLC-5 systems, simi
Publication 1785-UM024B-EN-P - January 2003GlossaryThis glossary is specific to ControlNet PLC-5 Hot Backup terms used in this manual. For a comprehe
Publication 1785-UM024B-EN-P - January 2003ii• ControlNet DIF and DOF files• ControlNet Configuration file• ControlNet Status file• ControlNet Diagnos
Publication 1785-UM024B-EN-P - January 2003iiiControlNet network address The address on the ControlNet network given to each node (also referred to a
Publication 1785-UM024B-EN-P - January 2003ivNote: When performing editing on either PLC-5, we recommend that you disable this feature first. This w
Publication 1785-UM024B-EN-P - January 2003vNnetwork update time (NUT)The repetitive time interval in which data can be sent on a ControlNet network.
Publication 1785-UM024B-EN-P - January 2003Table of Contents vQualification: From No Control State to Primary State . . B-6Qualification: From
Publication 1785-UM024B-EN-P - January 2003viQqualificationA phase of operation each PLC-5 goes through before being considered ready, or qualified, t
Publication 1785-UM024B-EN-P - January 2003viiswitchover The transfer of control from the primary PLC-5 to a qualified secondary PLC-5. This can occu
Publication 1785-UM024B-EN-P - January 2003viii
Publication 1785-UM024B-EN-P - January 2003IndexNumerics1747 adapter enhancements 2-41771 adapter enhancements 2-41785 firmware enhancements 2-41785-B
Publication 1785-UM024B-EN-P - January 20032 IndexControlNet, planning and installing P-3ControlNet, publications P-3ControlNet, related docume
Publication 1785-UM024B-EN-P - January 2003Index 3Nnew features of ControlNet Hot Backup 1no control backup state B-3node address settings 3-1O
Publication 1785-UM024B-EN-P - January 20034 Indexswitchover considerations B-16, E-2synchronizing programs D-1synchronous mode 3-18synchronous
Publication ICCG-5.21- January 2001 PN 955107-82How Are We Doing?Your comments on our technical publications will help us serve you better in the fut
Other CommentsPLEASE FOLD HERENO POSTAGE NECESSARY IF MAILED IN THE UNITED STATESBUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO. 18235 CLEVELAND OHPOST
Publication 1785-UM024B-EN-P - January 2003Table of Contents viSequential Process Application Considerations . . . . . . . . . . E-5What Caus
Publication 1785-UM024B-EN-P - January 2003 25 PN 957345-74Supersedes Publication 1785-6.5.24 - February 1999 Copyright © 2003 Rockwell Automation, In
1 Publication 1785-UM024B-EN-P - January 2003Chapter 1Backup Concepts for the ControlNet PLC-5 Hot Backup SystemChapter ObjectivesThis chapter describ
Publication 1785-UM024B-EN-P - January 20031-2 Backup Concepts for the ControlNet PLC-5 Backup SystemBasic System ArchitectureThe following ill
Publication 1785-UM024B-EN-P - January 2003Backup Concepts for the ControlNet PLC-5 Backup System 1-3QualificationWhen bringing the secondary p
Publication 1785-UM024B-EN-P - January 20031-4 Backup Concepts for the ControlNet PLC-5 Backup SystemEquivalence CheckingBackup systems are tra
Publication 1785-UM024B-EN-P - January 2003Backup Concepts for the ControlNet PLC-5 Backup System 1-5SwitchoverSwitchover is what occurs when t
Important User InformationBecause of the variety of uses for the products described in this publication, those responsible for the application and use
Publication 1785-UM024B-EN-P - January 20031-6 Backup Concepts for the ControlNet PLC-5 Backup SystemNotes
1 Publication 1785-UM024B-EN-P - January 2003Chapter 2Understanding the ControlNet PLC-5 Hot Backup System ComponentsChapter ObjectivesThis chapter de
Publication 1785-UM024B-EN-P - January 20032-2 Understanding the ControlNet PLC-5 Hot Backup System Components• ControlNet network cables, taps
Publication 1785-UM024B-EN-P - January 2003Understanding the ControlNet PLC-5 Hot Backup System Components 2-3Compatibility ConsiderationsIf th
Publication 1785-UM024B-EN-P - January 20032-4 Understanding the ControlNet PLC-5 Hot Backup System ComponentsSummary of Required Hardware, Fir
Publication 1785-UM024B-EN-P - January 2003Understanding the ControlNet PLC-5 Hot Backup System Components 2-5ControlNet Backup CartridgeEach C
Publication 1785-UM024B-EN-P - January 20032-6 Understanding the ControlNet PLC-5 Hot Backup System ComponentsNotes
1 Publication 1785-UM024B-EN-P - January 2003Chapter 3Installing and Configuring Your ControlNet PLC-5 Backup SystemChapter ObjectivesThis chapter out
Publication 1785-UM024B-EN-P - January 20033-2 Installing and Configuring Your ControlNet PLC-5 Backup System6. Wire the ControlNet network to
Publication 1785-UM024B-EN-P - January 2003Installing and Configuring Your ControlNet PLC-5 Backup System 3-3Configuring With a Single Control
Rockwell Automation SupportBefore you contact Rockwell Automation for technical assistance, we suggest you please review the troubleshooting informati
Publication 1785-UM024B-EN-P - January 20033-4 Installing and Configuring Your ControlNet PLC-5 Backup SystemThe Scanlist Configuration screen
Publication 1785-UM024B-EN-P - January 2003Installing and Configuring Your ControlNet PLC-5 Backup System 3-5The Connection Properties dialog b
Publication 1785-UM024B-EN-P - January 20033-6 Installing and Configuring Your ControlNet PLC-5 Backup SystemNote that the message number for t
Publication 1785-UM024B-EN-P - January 2003Installing and Configuring Your ControlNet PLC-5 Backup System 3-7Configure ControlNet I/O on the Se
Publication 1785-UM024B-EN-P - January 20033-8 Installing and Configuring Your ControlNet PLC-5 Backup SystemConfigure the Hot Backup Parameter
Publication 1785-UM024B-EN-P - January 2003Installing and Configuring Your ControlNet PLC-5 Backup System 3-9The ControlNet Hot Backup screen a
Publication 1785-UM024B-EN-P - January 20033-10 Installing and Configuring Your ControlNet PLC-5 Backup System1. In RSLogix 5, open the project
Publication 1785-UM024B-EN-P - January 2003Installing and Configuring Your ControlNet PLC-5 Backup System 3-11Configuring With Differing Applic
Publication 1785-UM024B-EN-P - January 20033-12 Installing and Configuring Your ControlNet PLC-5 Backup SystemThe Scanlist Configuration screen
Publication 1785-UM024B-EN-P - January 2003Installing and Configuring Your ControlNet PLC-5 Backup System 3-13The Connection Properties dialog
Notes
Publication 1785-UM024B-EN-P - January 20033-14 Installing and Configuring Your ControlNet PLC-5 Backup System6. Right click on the odd-numbere
Publication 1785-UM024B-EN-P - January 2003Installing and Configuring Your ControlNet PLC-5 Backup System 3-15The Scanlist Configuration screen
Publication 1785-UM024B-EN-P - January 20033-16 Installing and Configuring Your ControlNet PLC-5 Backup System5. Click the Online button to con
Publication 1785-UM024B-EN-P - January 2003Installing and Configuring Your ControlNet PLC-5 Backup System 3-179. Set the following:• Backup Fil
Publication 1785-UM024B-EN-P - January 20033-18 Installing and Configuring Your ControlNet PLC-5 Backup SystemAdvanced Configuration OptionsThe
Publication 1785-UM024B-EN-P - January 2003Installing and Configuring Your ControlNet PLC-5 Backup System 3-19• User Program Control for Comple
Publication 1785-UM024B-EN-P - January 20033-20 Installing and Configuring Your ControlNet PLC-5 Backup SystemSynchronous and Asynchronous Prog
Publication 1785-UM024B-EN-P - January 2003Installing and Configuring Your ControlNet PLC-5 Backup System 3-21You can change the operational mo
Publication 1785-UM024B-EN-P - January 20033-22 Installing and Configuring Your ControlNet PLC-5 Backup SystemEquivalent indicates that the two
Publication 1785-UM024B-EN-P - January 2003Installing and Configuring Your ControlNet PLC-5 Backup System 3-23Once you have selected the files
1 Publication 1785-UM024B-EN-P - January 2003PrefaceManual ObjectivesThis manual shows you how to set up and apply a ControlNetTM PLC-5® Hot Backup sy
Publication 1785-UM024B-EN-P - January 20033-24 Installing and Configuring Your ControlNet PLC-5 Backup SystemInvalid State ReasonIf the system
Publication 1785-UM024B-EN-P - January 2003Installing and Configuring Your ControlNet PLC-5 Backup System 3-25For the point-to-point DH+ networ
Publication 1785-UM024B-EN-P - January 20033-26 Installing and Configuring Your ControlNet PLC-5 Backup SystemRequalification of Dual Primary P
Publication 1785-UM024B-EN-P - January 2003Installing and Configuring Your ControlNet PLC-5 Backup System 3-27Downloading Editing ChangesDownlo
Publication 1785-UM024B-EN-P - January 20033-28 Installing and Configuring Your ControlNet PLC-5 Backup SystemNotes
1 Publication 1785-UM024B-EN-P - January 2003Chapter 4Using I/O in Your ControlNet Hot Backup SystemChapter ObjectivesThis chapter describes special c
Publication 1785-UM024B-EN-P - January 20034-2 Using I/O in Your ControlNet Hot Backup SystemThis non-redundant I/O should only be used when al
Publication 1785-UM024B-EN-P - January 2003Using I/O in Your ControlNet Hot Backup System 4-3Redundant connection parameters consist of:• Input
Publication 1785-UM024B-EN-P - January 20034-4 Using I/O in Your ControlNet Hot Backup System3. Use RSLogix5 to make all the desired I/O config
Publication 1785-UM024B-EN-P - January 2003Using I/O in Your ControlNet Hot Backup System 4-5OOV is done via a round-robin poll that runs in th
Publication 1785-UM024B-EN-P - January 2003Preface 2What This Manual ContainsRefer to the following table to guide you through the information
Publication 1785-UM024B-EN-P - January 20034-6 Using I/O in Your ControlNet Hot Backup SystemWith CIO read instructions, there are two possibil
Publication 1785-UM024B-EN-P - January 2003Using I/O in Your ControlNet Hot Backup System 4-7There are two areas of concern with HMI devices in
Publication 1785-UM024B-EN-P - January 20034-8 Using I/O in Your ControlNet Hot Backup SystemThe application must only gather data from the PLC
Publication 1785-UM024B-EN-P - January 2003Using I/O in Your ControlNet Hot Backup System 4-9This procedure assumes that the HMI knows which PL
Publication 1785-UM024B-EN-P - January 20034-10 Using I/O in Your ControlNet Hot Backup SystemNotes
1 Publication 1785-UM024B-EN-P - January 2003Chapter 5Monitoring and Troubleshooting Your ControlNet PLC-5 Hot Backup SystemChapter ObjectivesThis cha
Publication 1785-UM024B-EN-P - January 20035-2 Monitoring and Troubleshooting Your ControlNet PLC-5 Hot Backup SystemControlNet PLC-5 Backup-Sp
Publication 1785-UM024B-EN-P - January 2003Monitoring and Troubleshooting Your ControlNet PLC-5 Hot Backup System 5-3 Using the 1785-CHBM Cartr
Publication 1785-UM024B-EN-P - January 20035-4 Monitoring and Troubleshooting Your ControlNet PLC-5 Hot Backup SystemTroubleshooting the Invali
Publication 1785-UM024B-EN-P - January 2003Monitoring and Troubleshooting Your ControlNet PLC-5 Hot Backup System 5-5If you see reason code:Whi
Publication 1785-UM024B-EN-P - January 2003Preface 3Related PLC-5 PublicationsRelated documentation for ControlNet and other PLC-5 programmable
Publication 1785-UM024B-EN-P - January 20035-6 Monitoring and Troubleshooting Your ControlNet PLC-5 Hot Backup SystemTroubleshooting Qualificat
Publication 1785-UM024B-EN-P - January 2003Monitoring and Troubleshooting Your ControlNet PLC-5 Hot Backup System 5-7Troubleshooting Qualificat
Publication 1785-UM024B-EN-P - January 20035-8 Monitoring and Troubleshooting Your ControlNet PLC-5 Hot Backup SystemThis puts the system in a
Publication 1785-UM024B-EN-P - January 2003Monitoring and Troubleshooting Your ControlNet PLC-5 Hot Backup System 5-93 Backup state of the proc
Publication 1785-UM024B-EN-P - January 20035-10 Monitoring and Troubleshooting Your ControlNet PLC-5 Hot Backup System11 Equivalence checks; th
Publication 1785-UM024B-EN-P - January 2003Monitoring and Troubleshooting Your ControlNet PLC-5 Hot Backup System 5-1130 Accept Configuration C
Publication 1785-UM024B-EN-P - January 20035-12 Monitoring and Troubleshooting Your ControlNet PLC-5 Hot Backup System46 Qualification status.
Publication 1785-UM024B-EN-P - January 2003Monitoring and Troubleshooting Your ControlNet PLC-5 Hot Backup System 5-1353 Crossload Status. Thi
Publication 1785-UM024B-EN-P - January 20035-14 Monitoring and Troubleshooting Your ControlNet PLC-5 Hot Backup SystemNotes
1 Publication 1785-UM024B-EN-P - January 2003Appendix ASpecificationsSpecificationsThe following specifications are for the 1785-CHBM cartridge.Memory
Publication 1785-UM024B-EN-P - January 2003Preface 4For more information on any of the software components of the ControlNet PLC-5 backup syste
Publication 1785-UM024B-EN-P - January 2003A-2 SpecificationsNotes
1 Publication 1785-UM024B-EN-P - January 2003Appendix BBackup StatesChapter ObjectivesThis Appendix describes the possible backup states and backup st
Publication 1785-UM024B-EN-P - January 2003B-2 Backup StatesInvalid Backup StateWhen an improper backup configuration exists, the PLC-5 Control
Publication 1785-UM024B-EN-P - January 2003Backup States B-3– Maximum program scan time (invalid if greater than (128 x NUT) and synchronous op
Publication 1785-UM024B-EN-P - January 2003B-4 Backup StatesIf there is a valid partner PLC-5 ControlNet backup system, and the systems are con
Publication 1785-UM024B-EN-P - January 2003Backup States B-5Lonely Primary Backup StateThe Primary LED is solid green if there is at least one
Publication 1785-UM024B-EN-P - January 2003B-6 Backup StatesBackup State TransitionsIn the previous section, we described the possible states o
Publication 1785-UM024B-EN-P - January 2003Backup States B-7Qualification: From the No Control State to the Secondary StateThe backup state tra
Publication 1785-UM024B-EN-P - January 2003B-8 Backup States• Backup configuration parameters passed to qualifying systemAfter the qualifying P
Publication 1785-UM024B-EN-P - January 2003Backup States B-9There are 6 different areas in which equivalence checking can be performed:– Progra
1 Publication 1785-UM024B-EN-P - January 2003Summary of ChangesSummary of Changes The information below summarizes the changes to the ControlNet PLC-5
Publication 1785-UM024B-EN-P - January 2003B-10 Backup StatesNo SFC information is included in the Force Tables checksum. Also, note that you c
Publication 1785-UM024B-EN-P - January 2003Backup States B-11PLC, we recommend that you disable equivalence checking first to avoid the conditi
Publication 1785-UM024B-EN-P - January 2003B-12 Backup StatesThough the complete Status File is not crossloaded, there are six words in this fi
Publication 1785-UM024B-EN-P - January 2003Backup States B-13It may take many seconds for the Qualification State Data Table crossload to finis
Publication 1785-UM024B-EN-P - January 2003B-14 Backup StatesIf you selected the Designated Primary feature, and the odd node of the odd-even b
Publication 1785-UM024B-EN-P - January 2003Backup States B-15There are two categories for switchovers: • Qualified Switchovers• Unqualified Swi
Publication 1785-UM024B-EN-P - January 2003B-16 Backup Statesstatus tab of the ControlNet Hot Backup screen. Once the Forced Switchover is acti
Publication 1785-UM024B-EN-P - January 2003Backup States B-17If the output values in the data tables are different between the primary and seco
Publication 1785-UM024B-EN-P - January 2003B-18 Backup States– Problems with the ControlNet network which causes loss of the handshake connect
1 Publication 1785-UM024B-EN-P - January 2003Appendix CData Table CrossloadingChapter ObjectivesThis appendix provides you with reference information