Installing and Configuring Your ControlNet PLC-5 Backup System 3-17
9. Set the following:
Backup File - Enter an unused data file number. This creates
a 200-word integer file to be used as the ControlNet Backup
Configuration and Status file.
Odd Node Address - Enter the ControlNet node address
corresponding to the odd node processor.
Send Message - Enter the message number of the from the
Produce Buffer ID from the odd-numbered node address
(refer to the number you recorded on page 3-6.)
Receive Message - Enter the message number of the
Consume Buffer ID from the odd-numbered node address
(refer to the number you recorded on page 3-6.)
If your system is properly configured, the PRI and SEC LEDs on
the first processors backup cartridge are off.
10. Save the configuration.
11. Repeat steps 1 through 10 for the second processor, saving the
configuration under a different name.
The QUAL LED on both processors should now be yellow, and
you have a fully qualified backup system. If desired, you can
now go to Run mode.