Installation InstructionsPLC-5 Relay Cartridge(Cat. No. 1785-RC)The 1785-RC Relay Cartridge serves as an interface from the PLC-5 programmable control
3/&5HOD\&DUWULGJHThe following warnings apply to products having CSA certification for use in hazardous locations.Les avertissements su
3/&5HOD\&DUWULGJH SpecificationsBackplane Current 0.200A @ +5VdcNumber of Outputs 1 (N.O. Contact)Contact Rating120Vac 50/60Hz @ 0.500A
3/&5HOD\&DUWULGJHPublication 1785-IN001A-US-P - April 2000 PN 957236-76PLC-5 and RSLogix are trademarks of Rockwell Automation.CSA logo
3/&5HOD\&DUWULGJH,PSRUWDQW Use of the relay cartridge requires the Series E, revision E firmware release. If your processors are not al
3/&5HOD\&DUWULGJH Note: If the relay cartridge is not inserted into the PLC-5 processor, the processor will operate normally, but will no
3/&5HOD\&DUWULGJHWire the Relay Cartridge1. Detach the 4-pin clamp-style removable connector from the relay cartridge and connect wiring
3/&5HOD\&DUWULGJH Install Firmware and Apply PowerBefore you can use the relay cartridge, your processors must be at the Series E, revisi
3/&5HOD\&DUWULGJH,PSRUWDQW When the relay cartridge internal relay coil switches (from open to closed, or closed to open), you must wai
3/&5HOD\&DUWULGJH Status IndicatorsEuropean Union Directive ComplianceIf this product has the CE mark, it is approved for installation wi
3/&5HOD\&DUWULGJHThis product is intended for use in an industrial environment.Low Voltage DirectiveThis product is tested to meet Counc
3/&5HOD\&DUWULGJH CSA Hazardous Location ApprovalCSA Hazardous Location ApprovalApprobation d’utilisation dans des emplacements dangereux