7 2 Sinking Input / 2 Output Module
Publication 1792D-5.25- January 1999
Specifications
Auxiliary Power
Indication Status
None No Auxiliary Power
Green
Solid Auxiliary Power Present
I/O Status Indicators
Function Module Status Indicator Point Indicator Condition
Outputs Green
Green
None
Yellow
Output not energized
Output energized
Inputs Green
Green
None
Yellow
No valid input
Valid input
2 Input / 2 Output Module - Cat. No. 1792D-2B2LP
Sinking Input Specifications Max Min
Inputs per block 2 - 3 wire or dry contact PNP
Sensor Source Current (per input) 100mA -
On-state Voltage 25V dc 10V dc
Off-state Voltage 5V dc
On-state Current 10mA 2mA
Off-state Current 1.5mA
Sourcing Output Specifications Max Min
Outputs per block 2 labeled O0 and O1
Output Auxiliary Voltage 30V 10V
On-state Voltage Drop 1V -
On-state Current 0.3A -
Off-state Leakage 1.5mA -
Module Current (all outputs) 0.6A -
Surge Current - for 10ms,
repeatable every 2s
0.6A -
No Load Sense Current (On-state) 0.18A -
General Specifications
Indicators Network Status - red/green
Module Status - red/green
Auxiliary Power - green
Point LED - yellow