8 2 Sinking Input / 2 Output Module
Publication 1792D-5.25- January 1999 PN 955134-81
1999 Rockwell International. All Rights Reserved. Printed in USA
This product has been tested at an Open DeviceNet Vendor Association,
Inc. (ODVA) authorized independent test laboratory and found to comply
with ODVA Conformance Test Software Composite Test Version 11.
ArmorBlock, ArmorBlock LP2 and DeviceNetManager are trademarks of Rockwell Automation.
Communication Rate 125Kbps @ 500 meters(1600 feet) for thick
cable, flat media length 375 meters
250Kbps @ 200 meters(600 feet) for thick cable,
flat media length 150 meters
500Kbps @ 100 meters (330 feet) for thick
cable, flat media length 75 meters
DeviceNet Power Voltage
Current
25V dc
125mA (no sensors)
300mA (full load)
11V dc min
Auxiliary Power Voltage
Current
30V dc
0.6A max
10V dc
0.6A max
Dimensions (assembled to base)
Inches (Millimeters)
1.023H x 2.7w x4.72D
(26)H x (68.5)W x (120)D
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock Operating
Non-operating
Vibration
-25 to 60
o
(-13 to 140
o
F)
-25 to 80
o
C (-13 to 176
O
F)
Up to 100%
30g peak acceleration, 11 (+1) ms pulse width
50g peak acceleration, 11(+1)ms pulse width
Tested 10g @ 10-500Hz per IEC 68-2-6
Conductors Publication DN-6.7.2
Enclosure Meets or exceeds IP67
Agency Certification
(when product is marked)
CE marked for all applicable directives