10 ArmorBlock MaXum 8 Output Module Series B
Publication 1792D-IN003B-EN-P - September 2000
The following illustration describes module status indicators.
The following table describes the network and module status
indicator.
Net/Mod Status Indicator
Indication Status:
Off No power or auto bauding
Flashing Green/Off On line but not connected
Solid Green On line, link OK, connected
Flashing Red Recoverable fault - module configuration error
I/O connection fault - one or more I/O connections in the timed-out
state
Solid Red Unrecoverable fault
Communication failure - duplicate node address present or incorrect
baud rate
Green to Red to Off At powerup only - LED test
O-2
O-3
O-5
O-1 O-6
O-4
Logic Status
Net/Mod Status
O-0 O-7
Auxiliary Power
Point LED Indicator for
output 5
Point LED Indicator for
output 4
Point LED Indicator for
output 1
Point LED Indicator for
output 0
Connector G
Connector F
Connector B
Connector A
Module Status Indicators
LED Assignments
42337
Point LED Indicator for
output 2
Connector C
Point LED Indicator for
output 3
Connector D
Point LED Indicator for
output 6
Connector E
Connector H
Point LED Indicator for
output 7