Rockwell-automation 1792D-OB4D ArmorBlock MaXum 8 Output Module Series Manual de usuario Pagina 12

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 16
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 11
12 ArmorBlock MaXum 8 Output Module Series B
Publication 1792D-IN003B-EN-P - September 2000
Specifications
8 Output Module - Cat. No. 1792D-0B8D
Output Specifications Max. Min.
Outputs per block 8 sourcing outputs labeled O0 through O7
Output Auxiliary Voltage 30V 10V
On-state Voltage Drop 1V -
On-state Current 1A -
Off-state Leakage 1.5mA -
Module Current (all outputs) 4.0A -
Surge Current - for 10 ms,
repeatable every 2s
2.4A -
No Load Sense Current (On-state) 0.18A -
Indicators Net/Mod Status - red/green
Logic Status - red/green
Auxiliary Power - green
Point LED - yellow/orange/red
Communication Rate
125Kbps @ 500 meters (1600 feet)
for thick cable, flat media length 375
meters (1230 feet)
250Kbps @ 200 meters (600 feet) for
thick cable, flat media length 150
meters (492 feet)
500Kbps @ 100 meters (330 feet) for
thick cable, flat media length 75
meters (246 feet)
DeviceNet Power Voltage
Current
25V dc max
75mA
11V dc min
150mA
Auxiliary Power Voltage
Current
30V dc
4A
10V dc
4A
Dimensions (assembled to base)
inches - (millimeters)
1.9H x 2.7W x 6.85D
(48.26)H x (68.6)W x (174)D
Vista de pagina 11
1 2 ... 7 8 9 10 11 12 13 14 15 16

Comentarios a estos manuales