ArmorBlock MaXum 8 Output Module Series B 11
Publication 1792D-IN003B-EN-P - September 2000
The following table describes logic status indicators.
The following table describes auxiliary status indicators.
The following table describes I/O status indicators.
For more information on indications, see the Technical Data,
publication 1792-TD001B-EN-P.
Logic Status Indicators
State Status
Off Logic is disabled
Solid Green Logic is enabled
Flashing Green Local forces are applied and local logic is enabled
Auxiliary Status Indicators
Indication Status
None No Auxiliary power
Solid Green Auxiliary power present
I/O Status Indicators
Function Module Status Indicator Point Indicator Condition
Outputs Green
Green
Module Status blink red
Module Status blink red
Module Status blink red
Module Status blink red
None
Yello w
Orange
Red
Orange
Red
Output not energized
Output energized
Output shorted-auto restart
Output shorted-latching
output no load-auto restart
Output no load-latching
Comentarios a estos manuales