Publication 1794-UM066A-EN-P - February 2012
Install Your FLEX I/O Adapter 11
Connect Wiring
1. Connect an Ethernet network cable to the RJ45 connector (A).
2. Connect the redundant Ethernet network cable to the RJ45
connector (B).
WARNING: If you connect or disconnect wiring while the
field-side power is on, an electrical arc can occur. This could cause
an explosion in hazardous location installations. Be sure that
power is removed or the area is nonhazardous before proceeding.
ATTENTION: When connecting wiring, torque terminal screws C,
D, E and F to 0.8 Nm (7 lb-in.).
ATTENTION: If multiple power sources are used, do not exceed
the specified isolation voltage.
ATTENTION: Power wiring must be less than 10 m (32.8 ft.) in
length.
ATTENTION: Do not wire more than two conductors on any single
terminal.