FlexArmor Analog Input Module 5
Publication 1798-IN007A-EN-P - April 2002
4. Screw down the module retaining screws to ensure IP67
compliance.
Connect the Cordset to the FlexArmor Module
The module uses 5 pin micro (12mm) style PCB mounted connectors.
Four micro caps cover the I/O connectors on the module. Remove
the caps and connect your cables to the appropriate ports. Keep the
caps in place on any unused connector to maintain the IP67 rating.
A pinout diagram for the connectors is shown below.
IMPORTANT
Torque the screws to 0.5-0.7 Nm. (4.43 - 6.2
inch pounds).
Dust caps must have 4 inch pounds of torque
to maintain IP67 compliance.
ATTENTION
!
Make sure all connectors and caps are
securely tightened to properly seal the
connections against leaks and maintain IP67
requirements.
For maximum noise immunity, input and
output cable return wires must be properly
terminated. When inputs and outputs are
connected in loopback, return wires should
be connected together.
I/O cable length should be less than 30
meters.
42652
Female Input Micro-Connector
(View into Socket)
Pin 1 Sensor Power
Pin 2 Current Input
Pin 3 Sensor Common
Pin 4 Voltage Input
Pin 5 Not Used
Vista de pagina 4
1 2 3 4 5 6 7 8