
110 Rockwell Automation Publication 750COM-UM008A-EN-P - July 2012
Chapter 6 Using Explicit Messaging (Adapter mode only)
ControlLogix Controller Example Scattered Write Request Data
In this message example, we use the data structure in Figure 34 in the source tag
(Scattered_Write_Request) to write new values to these 32-bit REAL (floating
point) parameters:
See DPI Parameter Object
on page 163 (Class code 0x93) or Host DPI
Parameter Object on page 177 (Class code 0x9F) for parameter numbering.
Figure 34
shows the parameter values which, in this example, have been
converted using a UDDT to correctly write their values. COP (Copy)
instructions could have been used for this purpose instead of a UDDT. If the
parameters being written to are 32-bit integers, do not COP the data to a REAL
tag.
Figure 34 - Example Scattered Write Request Converted Data
ControlLogix Controller Example Scattered Write Response Data
The results of the message appear in the destination tag named
Scattered_Write_Response (Figure 35
). Values of “0” indicate no errors occurred.
Figure 35 - Example Scattered Write Response Data
PowerFlex 750-Series Drive Parameter Write Value
536 - [Accel Time 2] 11.1 Sec
538 - [Decel Time 2] 22.2 Sec
575 - [Preset Speed 5] 33.3 Hz
576 - [Preset Speed 6] 44.4 Hz
577 - [Preset Speed 7] 55.5 Hz
Comentarios a estos manuales