Rockwell Automation Publication 20P-IN010C-EN-P - February 2012 11
PowerFlex DC Drive Frame C Pulse Transformer Circuit Board
Step 4: Configure the New
Pulse Transformer
Board
The Pulse Transformer circuit board must be configured to match the drive size
(armature output current and HP rating). The steps required to complete the
configuration are different based on the revision code of the board. See either,
Pulse Transformer Board FIR3-XX Rev. “L” and Lower
below, or Pulse
Transformer Board FIR3-XX Rev. “M” and Higher on page 13.
Pulse Transformer Board FIR3-XX Rev. “L” and Lower
1. Cut and remove the appropriate sizing resistor(s) (if necessary) from the
Pulse Transformer board based on the drive size. Refer to Table 1 -
or Ta ble
2 - in the Sizing Resistor Configuration section on page 11 for the
appropriate configuration.
Sizing Resistor Configuration
The tables below indicate the value of the designated resistor (R1 - R5) when left
in place on the Pulse Transformer board, or indicate “Remove” when the resistor
should be cut off and removed from the board. “–” indicates that this resistor is
not contained on the Pulse Transformer board for the designated drive size.
Table 1 - 230V AC Input Drives
Table 2 - 460V AC Input Drives
IMPORTANT
This procedure requires a multimeter that measures resistance to thousandths
of an ohm.
Drive Current
Rating Code
DC
Amps
AC Line
Amps
HP R1 R2 R3 R4 R5
521 521 426 150 – Remove 5.36Ω 5.36Ω 5.36Ω
Drive Current
Rating Code
DC
Amps
AC Line
Amps
HP R1 R2 R3 R4 R5
495 495 404.4 300 – Remove 5.36Ω 5.36Ω 5.36Ω
667 667 544.9 400 – 5.36Ω 5.36Ω 5.36Ω 5.36Ω
=
Sizing resistors are located in the center
of the Pulse Transformer circuit board.
Comentarios a estos manuales