1-6 Getting Started
This section is provided to help experienced users quickly start using the
adapter. If you are unsure how to complete a step, refer to the referenced
chapter.
Quick Start
Step Action Refer to …
1 Review the safety precautions for the adapter. Throughout this manual
2 Verify that the PowerFlex drive is properly installed. Drive User Manual
3 Commission the adapter.
Set a unique MAC address and, depending on where the
PowerFlex drive nodes are located on the network,
appropriately set the TERM, -BIAS, and +BIAS switches.
Chapter 2
,
Installing the Adapter
4 Install the adapter.
Verify that the PowerFlex drive is not powered. Then,
connect the adapter to the drive using the Internal
Interface cable. Use the captive screw to secure and
ground the adapter to the drive.
When installing the adapter in a DSI External Comms Kit,
refer to the 22-XCOMM-DC-BASE Installation Instructions
(publication 22COMM-IN001) supplied with the kit.
PowerFlex 4-Class DSI
Network Communication
Adapter Installation
Instructions (publication
22COMM-IN002) and
Chapter 2
,
Installing the Adapter
5 Apply power to the adapter and verify key settings.
A. The adapter receives power from the drive. Verify
that the adapter is installed correctly and then apply
power to the drive. The PORT status indicator should
be solid green. If it is red, there is a problem. Refer to
Chapter 5
, Troubleshooting.
B. Verify/configure key adapter parameters.
C. Configure/verify key drive parameters.
Chapter 2
,
Installing the Adapter
6 Connect the adapter to the network.
Verify that the PowerFlex drive is not powered. Then,
connect the adapter to the network using a shielded,
twisted wire pair.
Chapter 2,
Installing the Adapter
7 Configure the adapter for your application.
Set adapter parameters for the following functions as
required by your application:
Fault actions
Baud rate
Chapter 3,
Configuring the Adapter
8 Configure the controller to communicate with the
adapter.
Use the controller’s programming software to program the
controller.
Instructions for your
controller’s programming
software
Vista de pagina 13