Rockwell-automation 22-COMM-B PowerFlex BACnet MS/TP Adapter Manual de usuario Pagina 48

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 72
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 47
5-4 Troubleshooting
If you encounter unexpected communications problems, the adapter’s
diagnostic items can help you or Rockwell Automation personnel
troubleshoot the problem. Adapter diagnostic items can be viewed using
a PowerFlex 4-Class HIM, DriveExplorer software (version 3.01 or
later), or DriveExecutive software (version 3.01 or later).
Table 5.A Adapter Diagnostic Items
Viewing Adapter Diagnostic Items
No. Name Description
1Reserved
2 Logic Cmd The present value of the Logic Command being transmitted to
the drive by the adapter.
3 Reference The present value of the Reference being transmitted to the
drive by the adapter.
4Reserved
5 Logic Sts The present value of the Logic Status being received from the
drive by the adapter.
6 Feedback The present value of the Feedback being received from the
drive by the adapter.
7 DSI Overrun Errs The number of DSI receive overrun errors.
8 DSI Framing Errs The number of DSI receive framing errors.
9 DSI CRC Errs The number of DSI receive CRC errors.
10 Boot Flash Count The number of times the boot firmware in this adapter has
been flash updated.
11 App Flash Count The number of times the application firmware in this adapter
has been flash updated.
12 MAC Addr SW The MAC address selected by the DIP switches (SW1…SW7)
on the adapter. This value is not latched when the adapter
powers up, and will update as the switch settings are
changed.
13 BN Rx Packets The number of BACnet packets received by the adapter.
14 BN Tx Packets The number of BACnet packets transmitted by the adapter.
15 BN Overrun Errs A count of the number of BACnet receive overrun errors.
16 BN Framing Errs A count of the number of BACnet receive framing errors.
17 BN CRC Errs A count of the number of BACnet receive CRC errors.
Vista de pagina 47
1 2 ... 43 44 45 46 47 48 49 50 51 52 53 ... 71 72

Comentarios a estos manuales

Sin comentarios