Publication IASIMP-QS015C-EN-P - August 2011 161
Logix Communication and Controller Configuration Appendix A
3. Double-click a request from
one of the devices.
4. Enter a unique IP address for
each device.
5. Click OK.
If you are not on an isolated
network, obtain the IP
addresses from your network
administrator.
6. Repeat steps 3…5 for each
device, except for the
PanelView Plus terminal.
7. Select the first device in the Relation
List field.
8. Click Disable BOOTP/DHCP.
9. Repeat steps 7…8 for all devices
except for the PanelView Plus
terminal.
10. Close the BOOTP/DHCP utility.
If prompted to save changes, click No.
IMPORTANT
If you cycle power, the device will not retain its IP address unless you disable BOOTP/DHCP.