172 Publication IASIMP-QS015C-EN-P - August 2011
Appendix A Logix Communication and Controller Configuration
6. Enter a Name for the module.
7. Enter the IP Address of your Logix
controller network module.
Refer to Browse the EtherNet/IP
Network Devices on page 168 for
the IP address.
8. From the Electronic Keying
pull-down menu, choose Disable
Keying.
If you are using a ControlLogix
controller, you will also need to
choose the module revision.
9. Clear Open Module Properties.
10. Click OK.