16 DCSNet/RE RIO Module
Publication 56AMXN-IN002A-EN-P November 2002
Message Description
Error: Heard Another RIO
Master
The module is configured as a Remote I/O master
and has heard another Remote I/O master active on
the network.
RIO Master The module is configured as a Remote I/O master.
Displayed during normal operation.
Drop x Config Mismatch The configuration for remote I/O drop x in Flash
memory on the module doesn’t match the drop on
the network.
Drop x OffLine Remote I/O drop x is offline.
RIO FLASH Config Invalid The module is configured as a Remote I/O master
and the configuration in FLASH memory is invalid.
Run 56AmxnRioCfg and configure the module.
Flash config drop mismatch Configuration in FLASH is incompatible with current
switch settings
Thumb Test Mode The module is in thumbwheel test mode.