AĆ1
Appendix A
Technical Specifications
Ambient Conditions
D Storage temperature: -40_ CĆ85_ C
D Operating temperature: 0_ CĆ60_ C
D Humidity: 5Ć90% nonĆcondensing
Maximum Module Power Dissipation
D 46 Watts
Dimensions
D Height: 11.75 inches
D Width: 1.25 inches
D Depth: 7.375 inches
System Power Requirements
D +5 volts: 425 ma
Input Circuit
D Number of inputs: 16
D Maximum operating voltage: 117 volts rms
D Minimum turnon voltage: 92 volts rms
D Maximum turnoff voltage: 32 volts rms at 50/60 hertz
45 volts DĆC
D Maximum offĆstate current: 3 ma
D Input current at 115V: 11.7 ma
D Maximum input delay: 20 msec at 50 hertz
18 msec at 60 hertz
ă8 msec at DĆC
D Four inputs per isolated common
D 2500 volt isolation between logic common and input power
D Maximum input wire length: 1000 feet