6.4. Serial port fatal error
6.5. Illegal interrupt on lower port of processor
6.6. Transmit interrupt error
6.7. Runbase integrity lost
6.8. Bad runbase checksum
6.9. Transmit buffer error
7.0. MultiĆprocessor runbase download in progress
7.1. Disconnect timeĆout during download
7.2. Spurious interrupt received
Corrective action: 6.3. may be caused by attempting AutoMax ONĆLINE
PROGRAMMING functions before the runbase is loaded onto the Processor
module(s) in the rack. In this case, exit the ONĆLINE PROGRAMMING menu and
download the runbase. 7.0 is a status message only. For all other error codes,
cycle power and try to load the runbase again.
Loading the Runbase over the Network
8.0. Bad message length specified for network message
8.1. Bad destination drop
8.2. Transmitting drop inactive
8.3. Destination port unallocated
8.4. Destination port busy
8.5. Did not receive expected response
8.6. Spurious network interrupt received
8.7. Network message is being transmitted
Corrective action: 8.0. and 8.1. are caused by a failed Processor in the leftmost
slot. For 8.2., check the coax cable; then try replacing the network module. For
8.3. Ć 8.5., check the destination Network module, then the leftmost Processor in
the destination rack. For 8.6. and 8.7., cycle power and try to load the runbase
again.
Miscellaneous Process Errors
8.8. Processor failure
Corrective action: replace Processor module.