EĆ2
1d Privilege violation detected
Ć runbase software fault
Ć bad Processor module
1E UnĆimplemented instruction detected
Ć runbase software fault
Ć bad Processor module
1F Illegal interrupt detected
Ć runbase software fault
Ć bad Processor module
30 Problem in application software
31 Bus error
Ć attempt to access invalid address
32 Define channel error
Ć problem in application software
33 Define scan error
Ć hardware fault
34 Memory integrity lost
Ć hardware fault
35 DC drive CML block initialization error
36 Communication between drive processor and I/O
controller lost
Ć hardware fault
37 DC drive I/O controller runĆtime board error
Ć hardware fault
38 UDC module generated a STOP ALL
39 UDC module interrupt allocation failed
3A Processor OS incompatible with UDC OS
Corrective action: correct the problem in application software. Try to reset by
cycling power and reĆloading configuration and application tasks. Replace the
Processor module. For error code 31, see JĆ3650; for error code 37, see JĆ3669.
For error code 17: If you define bits in a register that is also defined as a register,
neither the bits nor the register can be forced. For error code 38, examine the
error logs for all UDC tasks in the rack. Also, error code 38 can be caused by
enabling CCLK on more than one module in the rack. Verify that CCLK is enabled
on only one module. For error code 39, cycle power to the rack and reĆload the
configuration and application tasks.
BASIC STOP ALL Error Codes
The following error codes are caused by problems in BASIC tasks and cause all
tasks to stop.
40 Too many RETURNS from GOSUBs (or RETURN without GOSUB)
41 Illegal jump into a FOR loop
42 NEXT statement does not match current FOR
43 Invalid START EVERY statement
44 Invalid EVENT statement
45 STOP statement executed in application software
(causes a STOP ALL/CLEAR)
46 SET or WAIT attempted with no event definition
47 Task stack overflow
48 GOSUBs not balanced at END statement
49 Insufficient space for channel buffer
4A Attempted to execute undefined opcode
4B Attempted to execute nonĆexecutable opcode
4C Attempted to execute illegal opcode
4D RESTORE to nonĆDATA statement line number
4E Attempted to take square root of a negative number
4F Attempted to RESUME without being in an ON ERROR handler