3Ć5
Channel 0
Channel 1
Channel 2
Channel 3
-++-
Load
Source
IĆOut
Common
1
2
3
-++-
Load
Source
IĆOut
Common
4
5
6
IĆOut
Common
7
8
9
IĆOut
Common
10
11
12
-++-
Load
Source
-++-
Load
Source
Figure 3.2 Ć Typical Recommended Output Shielding Methods
Step 11. Turn off power to the Reliance device that will be
connected to the Analog Rail module.
Step 12. Set the Mode" switch on the faceplate of the Analog Rail
module to the desired position.
Step 13. Connect the I/O Rail cable between the Analog Rail
connection labeled Input" and an I/O port on the
Reliance device that will communicate with the module.
Turn on power to the Reliance device that will
communicate with the Analog Rail module. Recall that the
Mode switch is read each time the Reliance device
connected to the module is powered up.
Step 14. The Analog Rail installation is now ready for testing.
Inspect all work to assure that the installation has been
performed properly.
Step 15. Turn on power to the Input Power" wiring. Turn on power
to the external hardware. Recall that external hardware
being powered by the output of the Analog Rail module
must be in series with an external power supply. See
figure 3.2. See Appendix A for the power supply
specifications.