CĆ1

  
The following AutoMate program sequences can be used to interface to an
AutoMate Processor that does not support the AOUT block. Over a period of
four scans, the program below maps registers 40 through 43 to the four
channels of an Analog Rail module in Rail mode.
Registers Used
0 Register that is configured to be updated at the end of scan.
40 Value to output to channel 0
41 Value to output to channel 1
42 Value to output to channel 2
43 Value to output to channel 3
44 Counter to select channel to operate this scan
45 Coils
End of Scan
If counter = 0, then move the data in register 40 to register 0.
44.17
[Ă/Ă]
Ă45.00
(ăă)
EN MOVE EN
LENGTH: 1
SRC: 40
DEST: 0
44.16
[Ă/Ă]
If counter = 1, then move the data in register 41 to register 0.
44.17
[Ă/Ă]
Ă45.01
(ăă)
EN MOVE EN
LENGTH: 1
SRC: 41
DEST: 0
44.16
[Ă/Ă]