Operation
16 Pub #75054-004-08, March 2013
OUT/OUT2 Output/Output 2
Switching mode HYNO:
Hysteresis/NO
contact
HYNC:
Hysteresis/NC
contact
WINO:
Window/NO contact
WINC:
Window/NC contact
4...20 mA:
Analog mode (analog
output versions only)
Switch point
value
Switch point
0.5...100% URL in
increments of 0.1
°C
Reset point value Reset point 0...99.5%
URL in increments of
0.1
°C
Switch point
delay
Delay time 0...99 sec.
in increments of
0.1 sec.
Reset point delay Delay time 0...99 sec.
in increments of
0.1 sec.
Min. distance between SP and RSP:0.5°C/K (0.9°F)