837E Solid-State Temperature Sensors User Manual
Operation
Pub #75054-004-08, March 2013 17
4…20 Analog Output
Value for 4 mA
(LRV)
Enter lower range
value in increments
of 0.1
°C
Value for 20 mA
(URV)
Enter upper range
value in increments
of 0.1
°C
Temperature
applied for 4 mA
(LRV)
Use measured
temperature as
lower range value
Temperature
applied for 20 mA
(URV)
Use measured
temperature as
upper range value
Error current Current value in
event of error:
MIN = 3.6 mA
MAX = 21.0 mA
HOLD = last value
Range of adjustment: LRL = Lower Range Limit; URL = Upper Range Limit;
LRV = Lower Range Value; URV = Upper Range Value
Min. distance between SETL and SETU: 20°C/K (36°F)