46 Rockwell Automation Publication 842E-UM001A-EN-P May 2012
Chapter 7 Diagnostics and troubleshooting
Warnings
Supported warnings (attribute 47+48)
Alarms
The alarm type is coded in a bit field of attributes 44 and 45. If one of the bits is
listed below is set, the alarm flag (attribute 47) will also be set.
If, for example, the velocity or temperature drop below/exceed the limit values,
the warning flag is set (attribute 49 position sensor object).
In addition, the Net LED flashes red.
The warning type is coded in a bit field of attributes 47 and 48.
Note: The position value will continue to be correctly calculated; the encoder is
therefore still ready for operation.
Bit Warning Description
FALSE (0)
(47)
TRUE (1)
(47)
0 Frequency exceeded Max. velocity exceeded OK Exceeded
1 Light control reserve LED current critical OK Out of
range
2 CPU watchdog Not implemented Always 0
3 Operating time limit warning Operating time limit reached Always 0
4 Battery charge Not implemented Always 0
5 Reference point Not implemented Always 0
6 Minimum velocity flag Minimum velocity set-point reached OK Fall below
7 Maximum velocity flag Maximum velocity set-point reached OK Exceeded
8 Minimum acceleration flag Minimum acceleration set-point reached OK Fall below
9 Maximum acceleration flag Maximum acceleration set-point reached OK Exceeded
10 Position limits exceeded Max. position exceeded OK Exceeded
11 Reserved by CIP Always 0
12 Reserved by CIP Always 0
13 Vendor:
Temperature out of range
Temperature set-points reached OK Out of
range
14 Vendor: over / under voltage
(9.700…30.300mV)
voltage set-points reached OK Out of
range