Rockwell-automation 9301 Series RSView32 Users Guide Manual de usuario Pagina 239

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 769
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 238
Configuring data logging 7–39
Combining logging
You can combine periodic or on–change logging with on–demand
logging. This enables data to be captured at particular times, as well as
when a particular event occurs. 4.
To combine logging:
1. In the Data Log Setup editor, choose Periodic or On Change as
the log trigger.
2. Type the DataLogSnapshot <file> command or the
DataLogSnapshot * command anywhere an RSView32 command
or macro can be used.
Providing operators with a way to log on
demand
At runtime, operators might need to take a snapshot of data. To do
this, they need a way to issue the DataLogSnapshot <file> command
or the DataLogSnapshot * command. Possible methods include: 3.
creating a button object and using the command as the press
action—operators can then press the button to take a data log
snapshot
creating a display key or global key and using the command as the
press action—operators can then press a key to take a data log
snapshot
providing a command line—operators can then type the command
directly on the command line
Vista de pagina 238
1 2 ... 234 235 236 237 238 239 240 241 242 243 244 ... 768 769

Comentarios a estos manuales

Sin comentarios