E–4 RSView32 User’s Guide
Example: Bridging DH and DH+ networks
The following figure shows an RSView32 system connected to a DH+
network with a KT–family card. The local DH+ network is bridged to
a remote DH network, which is bridged to a second remote DH+
network. The 1785–KA interface modules are used to bridge the
networks.
The valid station entries for the various nodes in the figure are:
Station Address Valid Entries
14 14
220 7.220
21 7.310.21 or 7.321