Rockwell-automation 9301 Series RSView32 Users Guide Manual de usuario Pagina 572

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 769
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 571
16–10 RSView32 User’s Guide
TransType The type of alarm that was generated. The types are:
InAlmIn Alarm (severities 1 through 8)
OutAlmOut of Alarm
AckedAcknowledged
RmAckRemote Acknowledged
InFltIn Fault
OutFltOut of Fault
SupOnSuppress On
SupOfSuppress Off
TagName The name of the tag or alarm event that caused the
alarm.
TagValue The value of the tag at the time the alarm occurred.
TagType The type of tag in alarm: A for analog, D for digital, S for
string.
ThreshVal The threshold value.
ThreshNum The threshold number.
ThreshLabl The threshold label.
Severity The alarm severity (1 is highest severity and 8 is lowest
severity).
DstFlag The Daylight Savings Time (DST) flag, where Y means
DST is in effect and N means DST is not in effect. This
number is for RSView32 internal use only.
UserId The user that was logged on when the alarm occurred.
AlarmType The number RSView32 assigns to the transaction type.
Dscription The message that is associated with the transaction
(alarm) type.
This column Contains
Vista de pagina 571
1 2 ... 567 568 569 570 571 572 573 574 575 576 577 ... 768 769

Comentarios a estos manuales

Sin comentarios