Rockwell-automation AADvance Controller System Build Manual de usuario Pagina 52

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 130
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 51
3-8
Document: 553632
(ICSTT-RM448_EN_P) Issue: 08:
System Build Manual (AADvance Controller)
For each power supply connection, do the following:
Connect the negative line from the power supply, typically labelled '0V', to the left-
hand terminal.
Connect the positive line from the power supply, typically labelled '+24V', to the
right-hand terminal.
Apply a minimum tightening torque of 0.5 Nm (0.37 ft lb) to the terminal screws.
Note: Make sure that PWR-1 and PWR-2 are supplied from independent 24V dc
sources.
Refer to the illustration for an example.