Rockwell-automation Current Input Module Manual de usuario Pagina 23

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 66
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 22
4Ć5
      
Register 17 indicates the current status of each configured channel's
High alarm. See figure 4.3. A bit is set in this register whenever a
channel's input value exceeds the configured High alarm limit. The
bit is reset when the input value returns to a level below or equal to
the configured limit.
 
Bits 0Ć15
14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
RRRRRRRRRRRRRRRR
Bit 5 = Channel 5
Bit 6 = Channel 6
Bit 7 = Channel 7
Bit 8 = Channel 8
Bit 9 = Channel 9
Bit 10 = Channel 10
Bit 11 = Channel 11
Bit 12 = Channel 12
Bit 13 = Channel 13
Bit 14 = Channel 14
Bit 15 = Channel 15
Bit 0 = Channel 0
Bit 1 = Channel 1
Bit 2 = Channel 2
Bit 3 = Channel 3
Bit 4 = Channel 4
15
Figure 4.3 Ć High Alarm Status Register
      
Register 18 indicates the current status of each configured channel's
Low alarm. See figure 4.4. A bit is set in this register whenever a
channel's input value is less than the configured Low alarm limit. The
bit is reset when the input value returns to a level equal to or above
the configured limit.
 
Bits 0Ć15
14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
RRRRRRRRRRRRRRRR
Bit 5 = Channel 5
Bit 6 = Channel 6
Bit 7 = Channel 7
Bit 8 = Channel 8
Bit 9 = Channel 9
Bit 10 = Channel 10
Bit 11 = Channel 11
Bit 12 = Channel 12
Bit 13 = Channel 13
Bit 14 = Channel 14
Bit 15 = Channel 15
Bit 0 = Channel 0
Bit 1 = Channel 1
Bit 2 = Channel 2
Bit 3 = Channel 3
Bit 4 = Channel 4
15
Figure 4.4 Ć Low Alarm Status Register
Vista de pagina 22