
3 ● For Developers: Administering FactoryTalk Historian ActiveView
47
the primary server becomes available, FactoryTalk
Historian ActiveView reverts to the primary server.
RequirePrimary specifies that FactoryTalk
Historian ActiveView only connects to the primary
server in the collective.
Specifies how tags are resolved.
When set to 0, the default value, FactoryTalk
Historian ActiveView uses the saved Point ID over
the saved tag name. Use PB2TagResolution = 0,
when renaming Historian tags to resolve the tags
using the Point ID.
When set to 1, FactoryTalk Historian ActiveView
uses the saved tag name over the Point ID. use
PB2TagResolution = 1, when you want to use the
same tag but the tag has been moved from one
Historian Server (R&D) to another Historian
Server (Production)
When set to 0, XP themes are not supported. This
setting allows viewing the VBA color palette from
the Properties window.
The values in the following example are not necessarily the default values.
[Startup]
ToolbarVisibility = 0
Show Value Attributes = 1
ConnectUsingAPI = 0
[Trend Definition]
MarkerWarning = 1
UpdateTimeRange = 604800
[XYPlot Definition]
UpdateTimeRange = 604800
Comentarios a estos manuales