Chapter 1 Produce and Consume a Tag
Scenario 2
The RPI is outside the range of the producing controller’s RPI Limits.
There is no default RPI that is set up for the producing controller.
Version 17 and earlier: The RPI requested by the consumed tag is not within the
range of the producer. The connection is rejected and a 0111 error is reported that
the connection failed. You must re-enter an RPI that is within the range
configured on the produced tag. If a version 17 consumer is trying to connect with
a version 18 producer and the RPI is outside the range of the producer and there is
no default set up, a 0111 error reports the connection failed.
Tip:
See RPI I/O Faults on page 30
for an explanation of the error messages.
Version 18 and later: The RPI requested by the consumed tag is not within the
RPI limitation range of the producer. The producer is not set up to provide a
default RPI, so a 0111 error message is reported that the connection failed. You
must re-enter an RPI that is within the range configured for the producer because
there is no RPI default negotiation with the consumer.
26 Rockwell Automation Publication 1756-PM011F-EN-P - October 2014