Design a sequential function chart Chapter 1
The following table compares the different options for handling the last scan of a
step.
Characteristic During the last scan of a step, this option does
Don’t scan Programmatic reset Automatic reset
Execution actions
Only P and P0 actions execute. They execute
according to their logic.
All actions execute according to their logic.
P and P0 actions execute according to
their logic.
All other actions execute in Postscan
mode.
On the next scan of the routine, the P and
P0 actions execute in Postscan mode.
Retention of data values All data keeps its current values. All data keeps its current values.
Data reverts to its values for postscan.
Tags to the left of [:=] assignments clear
to zero.
Method for clearing data Use P and P0 actions. Use either of these.
Status bits of the step or action to
condition logic
P and P0 actions
Use either of these.
[:=] assignment (non-retentive
assignment)
Instructions that clear their data during
postscan
Reset of a nested SFC A nested SFCs remains at its current step. A nested SFCs remains at its current step.
For the Restart Position property, if you
choose the Restart at initial step option,
then these occur.
A nested SFC resets to its initial step
The X bit of a stop element in a nested SFC
clears to zero
Rock well Automati on Publication 1756-PM006F-EN-P - Oct ober 2014 37