Chapter 1 Design a sequential function chart
When the action is not on its last scan (conveyor_start.Q =1), this statement turns on conveyor_state. When
conveyor_state turns on, the conveyor turns on.
On the last scan of the action (conveyor_start.Q =0), this statement turns off conveyor_state. When
conveyor_state turns off, the conveyor turns off.
You can also use a P0 Pulse (Falling Edge) action to clear data (see Use the
programmatic reset option on page 38). This example uses an action to turn on a
conveyor at the start of a step. A different action turns off the conveyor at the end
of the step.
Example
This action turns on the conveyor. When conveyor_state turns on, the conveyor turns on.
Before the SFC leaves the step, the P0 action turns off the conveyor. On the last scan of the step,
conveyor_state turns off. This turns off the conveyor.
Use the automatic reset option
Automatic reset provides a system-defined cleanup of actions (known as postscan)
when they are shut down when any of the following occur.
transition out of the associated step
reset of a stored action
reset of an SFC routine
Postscan is similar to prescan in that most instructions are executed as if they are
FALSE. Some instructions have specific postscan behavior.
In RLL, OTE instructions are turned off and non-retentive timers are reset.
In structured text, the destination of a non-retentive assignment "[:=]" is
cleared.
A JSR instruction invokes its subroutine but parameters are not passed and
the logic in the subroutine is executed in postscan mode.
An Add-On Instruction executes its logic routine in postscan mode and
then executes its postscan logic in normal mode (if a postscan routine is
configured).
Any nested SFC (SFC that an action calls as a subroutine) is reset.
40 Rockwell Automation Publication 1756-PM006F-EN-P - October 2014