Chapter 2 Program a sequential function chart
1. Double-click the text area of the action.
2. Type the required structured text.
3. To close the text entry window, press Ctrl+Enter.
Call a subroutine in an action
Use a Jump to Subroutine (JSR) instruction to execute a subroutine when the
action is active.
1. In the SFC, right-click the action and then click Set JSR.
2. In the Routine box, click the down arrow and then click the routine that
you want to call.
3. To pass a parameter to the routine, click an empty Input Parameters box.
Click the down arrow and then click the tag that contains the parameter.
4. To receive a parameter from the routine, click an empty Return
Parameters box. Click the down arrow and then click the tag in which to
store the parameter from the routine.